STANDARD SPECIFICATIONS

  • MAX. TEMP: 250°F
  • MAX. STATIC PRESSURE . : 4" w.g
  • MAX. VELOCITY: 3500 f.p.m.
  • MINIMUM SIZE: 12" x 8" Single Blade
    12" x 12" Multi Blade.
  • FINISH: Standard Mill.
  • CONSTRUCTION: All welded. units over 48" wide, dual panel.
  • HARDWARE: Plated steel center brackets; brass pivots; 5/16" plated steel linkage rod. Dual linkage on panels 31" to 48" wide.
  • BEARINGS: 1/2" dia. I.D. ball bearings.
  • AXLES: 1/2" dia. C1018 steel cadmium plated steel continuous rods.
  • COUNTERWEIGHTS: 2" dia. hot rolled steel bar attached to counterbalance arms.
  • COUNTERBALANCE ARMS: 2" x 1/4" x 12" lg. hot rolled steel bar external to damper.
  • BLADES: 16 ga. galvanized steel with press formed "V" reinforcements.
  • FRAME: 12 ga. galvanized steel channel with 14 ga. galvanized press formed steel sub frame.
  • MAXIMUM SIZE: 72" x 60"

OPTIONS

  • -06 Blade Edge Seals

NOTES

  1. A & B are actual dimensions.
  2. Dual counterweights on units 5 blades and over (i.e., 36" and over).
  3. Dual linkage on panels over 30" wide.
  4. Counterweights are located on left-hand side when facing air leaving side
  5. Down Flow Models not available. Up Flow Model 3212 not shown.
  6. Counterweights must be field adjusted to system pressure.

User Notes

  1. Using the box below, write your notes.
  2. Click the 'Generate Savable Copy' button, which will pop up a new window with your notes in the text box.
  3. In the new window use the tool bar and choose 'File -> Save As' to save a copy of this webpage to your computer. Make sure you select the 'Save Complete Webpage' option, so the images are included.

You can now view and edit your notes on your copy of the webpage. To make additional changes to copy saved on your computer, follow the same process as outlined above.