Model 2740 Extruded Aluminum 4" Deep Stationary Blade @ 45°

CLICK HERE FOR PRINTABLE/ELECTRONIC SUBMISSION PDF

Vent_2740 Vent_2740dim1 Vent_2740dim2

STANDARD SPECIFICATIONS

  • FRAME: .080 6063T5 extruded aluminum.
  • BLADES: .080 6063T5 extruded aluminum
  • BIRDSCREEN: .051 x 3/4" diamond pattern expanded aluminum.
  • FINISH: Standard Mill.
  • MAXIMUM SINGLE SECTION: 72" x 96"
  • MINIMUM SIZE: 8" x 12"
  • NOTE: A and B are opening dimensions. Unless otherwise specified, louvers are made 1/4" undersize.

OPTIONS

  • -31 Flange.
  • -32 Multiple Section
  • -34 Buck Frame (Requires flanged louver).
  • -35 Sill Extension.
  • -40 Standard screen in removable frame.
  • -42 18 x 16 Mesh aluminum insect
  • -43 18 x 16 Mesh bronze insect screen
  • -44 1/2" x 1/2" x 16 Gauge S.S. Screen
  • -45 1/2" x 1/2" x .063 Aluminum screen
  • -85 .125 6063T6 extruded aluminum construction.
  • -89 Sleeve.
2740performance 2740air

Air Performance data reflects both intake and exhaust modes.

2740water

It is possible for moisture to penetrate louvers under adverse atmospheric
conditions. For critical applications, drained ductwork or other means of
drainage is recommended.

TEST UNIT SIZE 48" X 48" (15 Min. Duration)
Data shown does not include the effect of a birdscreen. Graphs are corrected to standard air density .075 lb. per cubic foot.
RECOMMENDED MAXIMUM INTAKE FREE AREA VELOCITY 700 F.P.M.


User Notes

  1. Using the box below, write your notes.
  2. Click the 'Generate Savable Copy' button, which will pop up a new window with your notes in the text box.
  3. In the new window use the tool bar and choose 'File -> Save As' to save a copy of this webpage to your computer. Make sure you select the 'Save Complete Webpage' option, so the images are included.

You can now view and edit your notes on your copy of the webpage. To make additional changes to copy saved on your computer, follow the same process as outlined above.